Size wire so it neither overheats nor drops too much voltage: choose a cross-section from the ampacity table, derate it for bundling or insulation (×0.80 for 2 cables bundled, ×0.70 for 3), and check voltage drop with V_drop = (2 × L × I × ρ) / A, using ρ = 0.0172 Ω·mm²/m. A 20 A load on 15 m of 2.5 mm² copper drops 4.1 V, which is 34% on a 12 V system but 1.7% on 240 V, which is why low-voltage DC needs much heavier wire. The fuse rating must never exceed the wire’s ampacity, so upgrade an undersized wire rather than enlarging the fuse.

How to select the correct conductor cross-section for a circuit based on current load, run length, and installation method.

Undersized Wire Overheats While Oversized Wire Only Wastes Metal

A wire that is too small for its load heats up. At moderate overloads, insulation degrades over months. At severe overloads, insulation melts in minutes and the wire becomes a fire igniter inside walls and conduit where it cannot be seen. Wire sizing is not a regulatory formality — it is the calculation that prevents buildings from burning.

Wire that is too large wastes copper, adds weight, and costs more — but causes no safety hazard. When in doubt, go larger. The cost of oversized wire is small compared to the cost of a fire.

Current Capacity: The Ampacity Table

Ampacity is the maximum continuous current a conductor can carry without exceeding its insulation’s temperature rating. It depends on:

  • Cross-section (larger = more current)
  • Insulation material (PVC rated 70°C; XLPE rated 90°C)
  • Installation method (clipped to surface radiates heat well; buried in insulation traps heat)

Copper conductor ampacity (approximate, 70°C PVC, in open air):

Cross-SectionCurrent CapacityTypical Use
0.75 mm²6 ALight-duty flex, lamp cord
1.0 mm²10 ALow-power circuits
1.5 mm²16 ALighting circuits
2.5 mm²25 AGeneral power circuits
4.0 mm²32 AHigh-power outlets, small appliances
6.0 mm²40 ALarge appliances, short sub-circuits
10 mm²54 ASub-panels, electric cookers
16 mm²73 ALarge motors, long runs
25 mm²95 AMain supply cables
35 mm²119 AHigh-current mains

Derating for Bundled or Buried Cables

Multiple cables bundled together or cables run inside thermal insulation cannot dissipate heat as well. Apply derating factors:

  • 2 cables bundled: multiply ampacity by 0.80
  • 3 cables bundled: × 0.70
  • 4–6 cables: × 0.57
  • Buried in insulation: × 0.50 or per specific cable datasheet

AWG Equivalents (American Wire Gauge)

AWG sizes run backwards — smaller number = larger wire:

AWGMetric EquivalentAmpacity (approx.)
180.75 mm²7 A
161.5 mm²13 A
142.5 mm²20 A
124.0 mm²30 A
106.0 mm²35 A
810 mm²50 A
616 mm²65 A
425 mm²85 A
235 mm²115 A

Voltage Drop Calculation

Beyond current capacity, wire must be sized to limit voltage drop over long runs. Thin wire has high resistance; high resistance causes voltage to drop between supply and load.

Formula: V_drop = (2 × L × I × ρ) / A

Where:

  • L = one-way length of run (meters)
  • I = current (amps)
  • ρ = resistivity of copper = 0.0172 Ω·mm²/m
  • A = conductor cross-section (mm²)
  • Factor of 2 accounts for outgoing and return conductors

Example: 20 A load, 15 m run, 2.5 mm² copper:

V_drop = (2 × 15 × 20 × 0.0172) / 2.5 = 10.32 / 2.5 = 4.1 V

On a 12 V system: 4.1 / 12 = 34% drop — completely unacceptable. On a 120 V system: 4.1 / 120 = 3.4% — borderline acceptable (3% preferred). On a 240 V system: 4.1 / 240 = 1.7% — excellent.

This calculation shows why low-voltage DC systems require much heavier wire for the same power.

Quick Reference: Maximum Run Length (3% Voltage Drop)

Current12 V24 V120 V240 V
10 A, 2.5 mm²2.7 m5.5 m27 m55 m
10 A, 6 mm²6.6 m13 m66 m132 m
10 A, 16 mm²17 m35 m175 m350 m
20 A, 6 mm²3.3 m6.6 m33 m66 m
20 A, 16 mm²8.8 m17.5 m88 m175 m

The practical lesson: for 12 V DC systems, keep runs under 5 meters with heavy wire, or step up to 24 V to allow longer runs with the same wire.

Sizing for Fuse Coordination

Wire and fuse must be coordinated: the fuse must blow before the wire overheats.

Rule: Fuse rating ≤ wire ampacity

Never install a larger fuse than the wire can carry. Common mistake: a 4 mm² circuit (rated 32 A) protected by a 63 A fuse “because the load needed it.” The fuse will not blow before the wire burns. Upgrade the wire size instead.

Wire SizeMaximum Fuse Rating
1.5 mm²16 A
2.5 mm²25 A
4.0 mm²32 A
6.0 mm²40 A
10 mm²50 A

Improvised Wire Sizing

When using salvaged or hand-drawn wire of unknown gauge, estimate cross-section by measuring diameter:

A = π × (d/2)² where d is measured with calipers.

A 2 mm diameter copper wire: A = π × (1)² = 3.14 mm² ≈ 2.5–4 mm² in practice. Use the lower ampacity table value for safety.

For hand-drawn wire from copper rod, the drawing gauge controls diameter. Keep notes on what gauge you drew and what load you assigned to it.