Size a house heat exchanger from its duty, its overall heat-transfer coefficient and the logarithmic mean temperature difference between the two streams: area = Q ÷ (U × LMTD). For 4 kW with district water entering at 80 °C and leaving at 45 °C, and the house loop heated from 40 to 70 °C in counterflow, the LMTD is 7.21 K, so a copper coil in a tank at an assumed U of 200 W/m²K needs 2.77 m² (about 59 m of 15 mm tube) and a plate exchanger at an assumed 1,000 W/m²K needs 0.55 m². A warmer primary return shrinks the area but raises the network’s return temperature.

Sizing the exchanger or coil that transfers heat from the village main to a house’s own heating loop.

The Equation

For a heat exchanger carrying duty Q between two streams, Q = U × A × LMTD, where U is the overall heat-transfer coefficient (W/m²K), A the heat-transfer area and LMTD the logarithmic mean temperature difference. For counterflow (the streams in opposite directions), with the temperature differences at the two ends ΔT_a and ΔT_b:

LMTD = (ΔT_a − ΔT_b) ÷ ln(ΔT_a ÷ ΔT_b)

When the two end differences are equal, LMTD is that value.

Worked Example: One House, Three Primary Return Temperatures

Inputs: Q = 4 kW; district water enters at 80 °C; the house loop is heated from 40 °C to 70 °C (flow 70, return 40); counterflow. Warm end difference: 80 − 70 = 10 K. Cold end difference: primary outlet − 40.

Primary outletCold end ΔTLMTDPrimary flowArea at U = 200Area at U = 1,000
45 °C5 K(10 − 5) ÷ ln 2 = 7.21 K0.027 kg/s2.77 m²0.55 m²
50 °C10 K10.0 K0.032 kg/s2.00 m²0.40 m²
55 °C15 K(15 − 10) ÷ ln 1.5 = 12.3 K0.038 kg/s1.62 m²0.32 m²

Working, first row: primary flow = 4 ÷ (4.18 × (80 − 45)) = 0.0273 kg/s; area = 4,000 ÷ (200 × 7.21) = 2.77 m²; a 15 mm copper tube has area π × 0.015 = 0.0471 m² per metre, so 2.77 ÷ 0.0471 = 59 m of tube.

The two U values are assumptions: 200 W/m²K for a coil in a tank where the tank side moves only by natural convection, and 1,000 W/m²K for a plate exchanger with forced flow on both sides. Neither is a corpus figure; both vary with design and fouling, and a bare copper coil measurement is the only way to know. Measure your first unit before building thirty (see below).

Reading The Table

  • Moving from a 55 °C to a 45 °C primary return raises the area by 12.3 ÷ 7.21 = 1.7 times. The cooler return saves pumping and loss but costs copper.
  • The cold-end approach, the gap between primary outlet and house return, is what the area depends on. A closer approach is cheaper to run and dearer to build.
  • A plate exchanger is far smaller than a coil: salvaged plate units from heating equipment are valuable for this reason (the carrier page notes this).

Method: Build And Measure A Coil

  1. Wind the coil from copper tube, with soldered or brazed joints (the temperatures, 230 to 350 °C and 600 to 900 °C, are in Metalworking & Soldering, which describes the work with a solar dish), inside an insulated tank, low in the tank so that the water it heats rises past the rest of the tank by natural convection.
  2. Fill both sides and vent the air.
  3. Run the primary at a known flow (bucket and stopwatch) and read the four temperatures.
  4. Compute the duty from the primary side, Q = m × c × (T_in − T_out), and divide by A × LMTD to get the real U.
  5. Use the measured U for the other houses, and size from it.

Pressure, Leaks And Separation

An exchanger has two sides; a pinhole leak lets water cross from the higher pressure to the lower. For a domestic hot water coil, keep the potable side at the higher pressure so a leak puts potable water into the loop and not the other way (a recalled convention), or use a double-wall unit where one is available. Salvaged plate units must be pressure-tested on both sides.

Common Mistakes

  • Using an arithmetic mean temperature difference. For a 10 K and 5 K end, the LMTD is 7.21 K; the arithmetic mean is 7.5 K, an error that grows with the range.
  • Sizing at the design temperature and running cooler. When the primary supply is lower than 80 °C the LMTD falls and the exchanger delivers less.
  • Ignoring fouling. Scale on the potable side cuts U with time.

Safety

Hot side meets drinking water

A cracked or corroded coil can put district water, with its rust and any treatment additives, into the house water, and 80 °C water into a tank rated for 60 °C. Keep district water chemically clean (no additives you would not drink), test the coil at 1.5 times pressure, and fit a relief on the house side.

What’s Next