Fire water has a hard physical floor: a litre that is heated from 20 C to 100 C and boiled absorbs at most 2.59 MJ, so a brigade line of 50-80 L/min can absorb at most 2.2-3.5 MW of fire, and wetting a wall that receives 12.5 kW/m² needs at least 0.29 L/min per m². Real water absorbs only a fraction of that, so at one-third efficiency the brigade holds about 0.7-1.2 MW, and a 5,000 L reserve wets 100 m² for anything from 10 to 172 minutes depending on how efficiently it is applied.

Water reserve sizing is the calculation of how many litres, and at what rate, a settlement must hold to fight a small fire and to wet the neighbours of a large one, using the heat that water can absorb.

Water Fights Fire By Absorbing Heat, So The Limit Is Physical

The fire guide asks for at least 200 L per cluster, ideally 1,000 L or more, and at least 5,000 L for a settlement of 150 people. It says 200 L cannot extinguish a fully involved structure but can contain a small fire and wet adjacent buildings. This article tests those numbers against the one thing that is certain: water works by taking up heat, and a litre can only take up so much. The standard values used (specific heat of water 4.18 kJ per kg per K, heat of vaporisation 2,257 kJ/kg) are recalled from physical tables and not read from this corpus.

Worked Example: Rate, Wall And Reserve

Heat absorbed per kilogram of water heated from 20 C to 100 C (80 K) and boiled: 80 × 4.18 + 2,257 = 2,591 kJ/kg = 2.59 MJ/kg. One litre is one kilogram. This is the ideal case in which every drop reaches the fire and evaporates; real efficiency η is below 1 and is the unknown.

What a brigade can absorb.

  1. 50 L/min = 0.833 kg/s; × 2.59 MJ/kg = 2.16 MW. 80 L/min = 1.333 kg/s; × 2.59 = 3.45 MW.
  2. At η = 1/3, one-third (an assumed round figure): 0.72 to 1.15 MW, about 0.7 to 1.2 MW.

So the brigade can at best hold a fire of 2.2 to 3.5 MW and realistically about one. The building-spacing article’s burning wall is a larger source than that, which is why the fire guide says to wet the neighbour and not fight the burning building. The charcoal forge’s own fire, about 42 kW at 5 kg an hour, is far inside the brigade’s reach (Fire Safety & Suppression).

Wetting a wall. Flux q on the wall in kW/m²; ideal water flow per m² = q ÷ 2,591 kJ/kg.

  1. At 12.5 kW/m² (the wood ignition level used in the spacing article, Fire Breaks & Building Spacing): 12.5 ÷ 2,591 = 0.00482 kg/s = 0.29 L/min per m². At 23 kW/m²: 0.53 L/min per m².
  2. A wall of 15 m² (5 m by 3 m) at 12.5 kW/m²: 15 × 0.29 = 4.3 L/min ideal, so 200 L lasts 46 minutes; at η = 1/3, 13 L/min and 15 minutes.

The efficiency problem. As I recall, exposure-protection sprinkler design uses on the order of 5 L/min per m² (about 0.1-0.15 US gallons a minute per square foot); I have not checked this against a standard. Against the ideal 0.29 at 12.5 kW/m² it implies η = 0.29 ÷ 5 = 6%, because most water runs off or falls where it absorbs nothing. Using it:

  1. The same 15 m² wall: 15 × 5 = 75 L/min, and 200 L lasts 2.7 minutes.
  2. 100 m² of wall and roof (an assumed exposed area) for 30 minutes: ideal 0.29 × 100 × 30 = 870 L; at η = 1/3, 2,600 L; at 5 L/min per m², 15,000 L.
  3. How long 5,000 L wets 100 m²: ideal 5,000 ÷ 29 = 172 minutes; at η = 1/3, 58 minutes; at 5 L/min per m², 5,000 ÷ 500 = 10 minutes.

The 5,000 L reserve is therefore adequate if water is placed well and marginal if it is not. That is a result about technique, which no formula can supply; it is measured in drills.

What You Need

  • The exposed area of each building a fire could threaten, in m², from the site plan
  • A bucket or hose and a timer for drills
  • A volume gauge: a marked barrel
  • The flux from the spacing article for the distance in question

Method: Size And Then Test

Step 1: Take the floor: exposed area × ideal L/min per m² × minutes you must protect. This is the least you could ever need.

Step 2: Divide by a pessimistic η (start at 1/3, and test lower).

Step 3: Drill. Wet a wall in the sun with a real bucket line for 10 minutes. Note how much water was used and whether the wall stayed wet.

Step 4: Set the reserve from the drill result, never below the fire guide’s 200 L per cluster and 5,000 L for 150 people, and set the refill rule.

Step 5: Place the water within 30 m of every building (Water Systems for Fire Fighting).

Common Mistakes

  • Taking the heat-absorption figure as the working rate. It is the lower bound.
  • Counting the reserve as usable in full. Some is dead volume, and a frozen barrel is nothing.
  • Sizing for one fire. Several roofs may need wetting at once in an ember storm.
  • Skipping the drill. Without it the efficiency is a guess.

Safety

A reserve is not a reason to stay

Having water does not make a well-alight building safe to fight. The numbers say a brigade holds a small fire and not a large one. If the fire is past the first minutes, get everyone out, count them and wet the neighbours from a distance (Response Protocols & Training).

What’s Next