Wire Sizing
How to select the correct conductor cross-section for a circuit based on current load, run length, and installation method.
Why This Matters
A wire that is too small for its load heats up. At moderate overloads, insulation degrades over months. At severe overloads, insulation melts in minutes and the wire becomes a fire igniter inside walls and conduit where it cannot be seen. Wire sizing is not a regulatory formality — it is the calculation that prevents buildings from burning.
Wire that is too large wastes copper, adds weight, and costs more — but causes no safety hazard. When in doubt, go larger. The cost of oversized wire is small compared to the cost of a fire.
Current Capacity: The Ampacity Table
Ampacity is the maximum continuous current a conductor can carry without exceeding its insulation’s temperature rating. It depends on:
- Cross-section (larger = more current)
- Insulation material (PVC rated 70°C; XLPE rated 90°C)
- Installation method (clipped to surface radiates heat well; buried in insulation traps heat)
Copper conductor ampacity (approximate, 70°C PVC, in open air):
| Cross-Section | Current Capacity | Typical Use |
|---|---|---|
| 0.75 mm² | 6 A | Light-duty flex, lamp cord |
| 1.0 mm² | 10 A | Low-power circuits |
| 1.5 mm² | 16 A | Lighting circuits |
| 2.5 mm² | 25 A | General power circuits |
| 4.0 mm² | 32 A | High-power outlets, small appliances |
| 6.0 mm² | 40 A | Large appliances, short sub-circuits |
| 10 mm² | 54 A | Sub-panels, electric cookers |
| 16 mm² | 73 A | Large motors, long runs |
| 25 mm² | 95 A | Main supply cables |
| 35 mm² | 119 A | High-current mains |
Derating for Bundled or Buried Cables
Multiple cables bundled together or cables run inside thermal insulation cannot dissipate heat as well. Apply derating factors:
- 2 cables bundled: multiply ampacity by 0.80
- 3 cables bundled: × 0.70
- 4–6 cables: × 0.57
- Buried in insulation: × 0.50 or per specific cable datasheet
AWG Equivalents (American Wire Gauge)
AWG sizes run backwards — smaller number = larger wire:
| AWG | Metric Equivalent | Ampacity (approx.) |
|---|---|---|
| 18 | 0.75 mm² | 7 A |
| 16 | 1.5 mm² | 13 A |
| 14 | 2.5 mm² | 20 A |
| 12 | 4.0 mm² | 30 A |
| 10 | 6.0 mm² | 35 A |
| 8 | 10 mm² | 50 A |
| 6 | 16 mm² | 65 A |
| 4 | 25 mm² | 85 A |
| 2 | 35 mm² | 115 A |
Voltage Drop Calculation
Beyond current capacity, wire must be sized to limit voltage drop over long runs. Thin wire has high resistance; high resistance causes voltage to drop between supply and load.
Formula: V_drop = (2 × L × I × ρ) / A
Where:
- L = one-way length of run (meters)
- I = current (amps)
- ρ = resistivity of copper = 0.0172 Ω·mm²/m
- A = conductor cross-section (mm²)
- Factor of 2 accounts for outgoing and return conductors
Example: 20 A load, 15 m run, 2.5 mm² copper:
V_drop = (2 × 15 × 20 × 0.0172) / 2.5 = 10.32 / 2.5 = 4.1 V
On a 12 V system: 4.1 / 12 = 34% drop — completely unacceptable. On a 120 V system: 4.1 / 120 = 3.4% — borderline acceptable (3% preferred). On a 240 V system: 4.1 / 240 = 1.7% — excellent.
This calculation shows why low-voltage DC systems require much heavier wire for the same power.
Quick Reference: Maximum Run Length (3% Voltage Drop)
| Current | 12 V | 24 V | 120 V | 240 V |
|---|---|---|---|---|
| 10 A, 2.5 mm² | 2.7 m | 5.5 m | 27 m | 55 m |
| 10 A, 6 mm² | 6.6 m | 13 m | 66 m | 132 m |
| 10 A, 16 mm² | 17 m | 35 m | 175 m | 350 m |
| 20 A, 6 mm² | 3.3 m | 6.6 m | 33 m | 66 m |
| 20 A, 16 mm² | 8.8 m | 17.5 m | 88 m | 175 m |
The practical lesson: for 12 V DC systems, keep runs under 5 meters with heavy wire, or step up to 24 V to allow longer runs with the same wire.
Sizing for Fuse Coordination
Wire and fuse must be coordinated: the fuse must blow before the wire overheats.
Rule: Fuse rating ≤ wire ampacity
Never install a larger fuse than the wire can carry. Common mistake: a 4 mm² circuit (rated 32 A) protected by a 63 A fuse “because the load needed it.” The fuse will not blow before the wire burns. Upgrade the wire size instead.
| Wire Size | Maximum Fuse Rating |
|---|---|
| 1.5 mm² | 16 A |
| 2.5 mm² | 25 A |
| 4.0 mm² | 32 A |
| 6.0 mm² | 40 A |
| 10 mm² | 63 A |
Improvised Wire Sizing
When using salvaged or hand-drawn wire of unknown gauge, estimate cross-section by measuring diameter:
A = π × (d/2)² where d is measured with calipers.
A 2 mm diameter copper wire: A = π × (1)² = 3.14 mm² ≈ 2.5–4 mm² in practice. Use the lower ampacity table value for safety.
For hand-drawn wire from copper rod, the drawing gauge controls diameter. Keep notes on what gauge you drew and what load you assigned to it.